logo
  • English
Home ProductsLow Temperature Chiller

Portable Low Temperature Chiller 25 Ton Reliable With Touch Screen

Certification
China Dongguan Ruixiang Machinery Co., Ltd certification
I'm Online Chat Now

Portable Low Temperature Chiller 25 Ton Reliable With Touch Screen

Portable Low Temperature Chiller 25 Ton Reliable With Touch Screen
Portable Low Temperature Chiller 25 Ton Reliable With Touch Screen

Large Image :  Portable Low Temperature Chiller 25 Ton Reliable With Touch Screen

Product Details:
Brand Name: Ruixiang
Certification: ISO9001/CE
Model Number: RX-25HP
Payment & Shipping Terms:
Minimum Order Quantity: 1 set
Price: RMB 6500-800000/PC
Packaging Details: Wooden Box Packaging
Delivery Time: 15-20 Units
Payment Terms: T/T
Supply Ability: 500days

Portable Low Temperature Chiller 25 Ton Reliable With Touch Screen

Description
Temperature Range: -80°C To 10°C Cooling Method: Air-cooled, Water-cooled
Refrigerant: R404A, R134a, R407C, Etc. Display: Digital Display, Touch Screen
Weight: 100kg To 500kg Safety Protection: High And Low Pressure Protection, Water Flow Protection, Overload Protection
Power Supply: 220V/50Hz, 380V/50Hz
Highlight:

25 Ton lab water chiller

,

Portable lab water chiller

,

25 Ton Low Temperature Chiller

Portable 25 ton low temperature chiller 25 HP glycol chiller

 

Product Description

Portable25 Ton Air Cooled Chiller Glycol Water Chiller Low Temperature Water Chiller Laboratory Low Temperature Circulation

Low Temperature Glycol Chiller
Low temperature glycol chiller is a kind of water cooling equipment, it can provide a constant temperature, constant current, constant pressure of a cooling equipment. The glycol chiller water is between -5℃ and -40℃ and the chilled water will be transported to the equipment or products that need cooling through chiller pump.

Air-cooled chiller is built-in insulation water tank and water pump, no need to add another cooling tower to heat. It is very easy to install and move. But it has high requirements on the working environment. It is cooled by hot air circulation, so if the ventilation effect of the installation workshop is not good, it will directly affect the refrigeration effect of the chiller.

Application
Industrial glycol water chiller unit is used to cool the hot parts of the equipment, so that the equipment can work normally at low temperature. Used in Beverage filling, spindle cooling, CNC machine tools, grinding miller, reaction system, welding machine, cutting machine and other equipment, temperature adjustment range can be 40 degrees below zero.

Specification

Model

 

AC-25L

nominal cooling capacity kcal/h 10570
  kw 12.29
input power kw 22.55
power supply 3PH~380V 50HZ
refrigerant type R404a
  type of control expansion valve
compressor type hermetic scroll(piston)
  power(kw) 18.75
condenser type finned copper tube + low noise outer rotor fan
evaporator type Plate heat exchanger
  chilled fluid flow (m3/h) 5.94
  inlet and outlet pipe diameter (inch) 2-1/2
pump power (kw) 2.2
  lift(m) 20
safety protection compressor over temperature, over current, high and low pressure, over temperature, flow switch, phase sequence, phase-missing, exhaust overheating, anti-freezing
dimension mm 2000*1130*2000
weight kg 920


The nominal cooling capacity is according to: Inlet chilled fluid temperature: -20℃,outlet chilled fluid temperature: -25℃Note:
Features of glycol cooling system

  • The glycol small water chiller use semi-closed piston compressor, high refrigeration efficiency, excellent performance.
  • Glycol solution can be used as a secondary refrigerant. The industrial glycol chiller outlet temperature of chilled water can reach -40 ℃.
  • The COP efficiency of air cooled glycol water chiller is about 2.6-3.3. According to the industrial needs, it can be refrigerated or heated, which is more used in general laboratories and small production lines.
  • The COP efficiency of water-cooled chiller is relatively high, about 4-5.5, which is used in industrial process cooling and large-scale construction projects.
  • Compared with the high efficiency wate cooled chiller, the air-cooled chiller is only different from the condenser. The low-temperature air-cooled chiller dissipates heat directly through the fan, while the water-cooled chiller takes away the heat from the condenser through cold water and dissipates heat through the cooling tower.
  • The water cooled low temperature water chiller can only refrigeration, if the need for heating, need other heating equipment.


The proportion of Ethylene Glycol Aqueous Solution of glycol water chiller unit

Operating temperature Concentration Density Specific heat capacity Heat conductivity Viscosity Freezing point
% ×10³ Kg/m³ KJ/(kg.k) W/m.k Pa.s
0 25 1.03 3.834 0.511 3.8 -10.6
-10 35 1.063 3.561 0.4726 7.3 -17.8
-20 45 1.08 3.312 0.441 21 -26.6
-30 55 1.097 2.975 0.3725 90 -41.6
 

Contact Details
Dongguan Ruixiang Machinery Co., Ltd

Contact Person: Mr. Toms li

Tel: 17388732852

Fax: 86-0769-86666173

Send your inquiry directly to us (0 / 3000)